3.1.2 When an Error Occurred
U5: there are 2 main remote controllers when power is turned ON
Change the setting from Main to Sub on the remote controller you want to be Sub.
U8: there are 2 sub remote controllers when power is turned ON
Change the setting from Sub to Main on the remote controller you want to be Main.
How to confirm Main/Sub setting
The Main/Sub setting of the remote controller is displayed on the bottom of the screen while
Checking the connection. Please stand by.
is displayed.
How to change Main/Sub setting
You may change the Main/Sub setting of the remote controller while
Checking the connection.
Please stand by.
is displayed by pressing and holding the
Mode Selector
button for 4 seconds or
longer.
1. It is not possible to change the Main/Sub setting from Main to Sub when only one remote
controller is connected.
2. When 2 remote controllers are being used, it is not possible to change the setting from Main to
Sub if one of the remote controllers is already set as Main.
Checking the connection.
Please stand by.
Main RC
Confirm the remote controller
Main/Sub setting after po
w
er
is turned O
N
.
Checking the connection.
Please stand by.
Error Code: U5
Main RC
Press and hold for 4 seconds
or longer the Mode Selector
button of sub remote
controller side.
Checking the connection.
Please stand by.
Sub RC
Fan
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...