SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
178
1.4.42 Setback Availability
For BRC1E73 only
Select the operation mode in which the setback function is available.
: Factory setting
1.4.43 Setting "Restricted/Permitted" for Airflow Block
For units with the infrared presence/floor sensor only
The airflow block function cannot be enabled when closure material kit, fresh air intake kit,
separately installed natural evaporation type humidifier, or branch air duct is equipped, due to the
possibility of dew condensation.
This setting restricts the airflow block function, preventing that the airflow block is inadvertently set
to ON. Ensure that "Airflow block restricted" is set when using the options listed above.
: Factory setting
1.5 Field Settings of Low-Temperature Hydrobox
Regarding the field settings of the low-temperature hydrobox (HXY-TA), refer to the service manual
SiUS392016EA.
Mode
No.
First Code
No.
Second Code
No.
Contents
1e
2
01
N/A
02
Heat only
03
Cool only
04
Cool/heat
Mode
No.
First Code
No.
Second Code
No.
Contents
1e
14
01
Airflow block permitted
02
—
03
—
04
—
05
Airflow block restricted
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...