Troubleshooting by Error Code
SiUS342303E
347
Part 6 Service Diagnosis
Indication after
la
u
nch test
operation?
U4-03
The PCB of indoor
u
nits
displaying
U9
are normal.
Check for indoor
u
nits of
other systems to tro
ub
leshoot
them according to rele
v
ant
error codes.
NO
YES
Check controller indoor
u
nits :
(1) Some error a
b
o
u
t
thermistor, or fan motor
(M1F, M2F), electronic
expansion
v
al
v
e, or
defecti
v
e PCB.
(2) Test operation was
interr
u
pted
b
y the
MODE
(BS1)
bu
tton.
YES
Check all indoor error
indication.
NO
Operate all indoor
u
nits.
YES
Do all
u
nits display
U9
?
Carry o
u
t the diagnosis again
after a lapse of 2 min
u
tes or
more.
NO
Did 2 min
u
tes or more
elapse after
U9
is
displayed?
Are the
indoor-o
u
tdoor
and o
u
tdoor-o
u
tdoor
transmission wirings
normal?
Disconnect
the o
u
tdoor-o
u
tdoor
transmission wiring.
Does the system normally
operate with a single
transmission
line?
Modify the transmission
wirings.
Replace the o
u
tdoor
u
nit main
PCB (A1P).
Mo
u
nt the DIII-NET extension
adaptor.
NO
NO
YES
YES
A
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...