Troubleshooting by Error Code
SiUS342303E
317
Part 6 Service Diagnosis
Note(s)
Reference
3.44 Thermistor Abnormality
Applicable
Models
All outdoor unit models
Error Code
H1, H9, J3, J5, J6, J7, J8, J9
Method of Error
Detection
Detect according to temperature detected with individual thermistors.
Error Decision
Conditions
The system is in operation and the thermistor causes wiring disconnection or short circuit in it.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit PCB
Troubleshooting
1. Check the error code and sub code, and replace the corresponding thermistor.
CHECK 11
Refer to page 381.
Thermistor is
connected to the
connector.
Replace the outdoor unit PCB.
Connect the connector and turn
ON again.
NO
NO
Replace the thermistor (
1).
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit PCB.
CHECK 11
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...