SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
294
Note(s)
1. Infrared presence sensor PCB and connector
Diagnosis procedure 1
Infrared presence sensor
error (Error code
CE-01
)
Turn off the power and then reconnect.
Check infrared presence sensor output; refer to
sensor and address data No. 22-25.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared presence
sensor PCB and the
connector (
1)
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
15
by the above
verification
method.
Normal.
NO
Displays
CE-01
again or
15
for
sensor and
address data.
Replace the sensor.
Model
Infrared presence
sensor PCB
Connector
FXFQ-T
A4P
X2A (A2P)
FXZQ-TB
A5P
X81A (A1P)
FXUQ-PA
A4P
X81A (A1P)