SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
326
3.50.2 Inverter Radiation Fin Temperature Rise Abnormality (Fan PCB)
Applicable
Models
All outdoor unit models
Error Code
L4
Sub code: 06, 07, 18, 19
Method of Error
Detection
Fan PCB radiation fin temperature is detected by the thermistor located inside the fan PCB circuit.
Error Decision
Conditions
Detected temperature exceeds a certain level.
Supposed
Causes
Radiation fin plate not fixed with screws
U0
error
Defective fan PCB
High outdoor air temperature
Troubleshooting
Continue operation.
Field factor. Radiation fin temperature
may have risen due to high outdoor air
temperature.
Turn ON the
power supply, and
then press the ON button.
Does the error
recur?
Replace the fan PCB.
YES
Rectify troubles.
Normal?
NO
Check for the cooling
conditions of radiation fin
used to cool the inverter.
(1) Is the radiation fin plate
fixed with screws?
(2) Error code
U0
is displayed
on the Error History
screen.
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...