SiUS342303E
Special Control
Part 4 Functions and Control
118
7.3 Defrost
Operation
To defrost the outdoor heat exchanger while in Evaporator, the defrost operation is conducted to
recover the heating capacity.
Tb: Heat exchanger deicer temperature
Part name
Electric
symbol
Function of functional part
Compressor motor
M1C, M2C
RXYQ72AA: 127.3 rps
RXYQ96/120AA: 125.4 rps + 140.0 rps
RXYQ144/168AA: 85.2 rps + 114.9 rps
RXYQ192/216/240AA: 135.0 rps + 140.0 rps
Fan motor
M1F, M2F
With high pressure
OFF
↔
Step 4
↔
Step 6
Electronic expansion valve (Heat exchanger main)
Y1E
100%
Electronic expansion valve (Heat exchanger left)
Y6E
Electronic expansion valve (Refrigerant cooling IPM)
Y2E
Same as normal control
Electronic expansion valve (Subcooling heat exchanger)
Y3E
Discharge temperature control
Electronic expansion valve (Refrigerant auto charge)
Y4E
Minimum pulse
Electronic expansion valve (Refrigerant cooling air)
Y5E
Same as normal control
Solenoid valve (Oil separator oil return)
Y1S, Y2S
ON
Solenoid valve (Hot gas bypass)
Y3S
ON
Solenoid valve (Accumulator oil return)
Y4S
ON
Solenoid valve (Four way valve)
Y5S
OFF
Solenoid valve (Injection)
Y6S
ON
Ending condition
A lapse of 15 minutes
Tb > 11°C (51.8°F) continues for 60 seconds or more
OR
Indoor unit actuator
Defrost operation
Fan
Thermostat ON unit
OFF
Non-operating unit
OFF
Thermostat OFF unit
OFF
Electronic expansion valve
Thermostat ON unit
Defrost EV opening degree
Non-operating unit
Defrost EV opening degree
Thermostat OFF unit
Defrost EV opening degree
Low-temperature hydrobox unit actuator
Oil return operation
Pump
Thermostat ON unit
Normal control
Non-operating unit
Normal control
Thermostat OFF unit
Normal control
Electronic expansion valve
Thermostat ON unit
0 pulse
Non-operating unit
0 pulse
Thermostat OFF unit
0 pulse
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...