![Daikin VRV EMERION RXYQ-AATJA Service Manual Download Page 395](http://html2.mh-extra.com/html/daikin/vrv-emerion-rxyq-aatja/vrv-emerion-rxyq-aatja_service-manual_4706199395.webp)
SiUS342303E
Check
Part 6 Service Diagnosis
388
4.12 Fan Motor Connector Check (Signal Cable)
CHECK 17
Resistance measuring points and judgment criteria.
Indoor Unit
FXFQ-T, FXZQ-TB, FXSQ05-48TB, FXMQ07-12PB, FXMQ15-24TB, FXAQ-P
FXEQ-P, FXUQ-PA
White
Orange
Brown
Blue
—
—
Red
(1)
(2)
(3)
(4)
(5)
(6)
(7)
FG
Vsp
Vcc
GND
—
—
Vdc
Measuring points
Judgment criteria
1 - 4
1
or more
2 - 4
1
or more
3 - 4
1
or more
7 - 4
1
or more
— (1)
White (2)
Orange (3)
Brown (4)
Blue (5)
— (6)
— (7)
Red (8)
—
FG
Vsp
Vcc
GND
—
—
Vdc
Measuring points
Judgment criteria
2 - 5
1
or more
3 - 5
1
or more
4 - 5
1
or more
8 - 5
1
or more
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...