Main/Sub Setting
SiUS342303E
81
Part 3 Remote Controller
3. Main/Sub Setting
3.1 BRC1E73
The Main/Sub setting is necessary when 1 indoor unit is controlled by 2 remote controllers. When
you use 2 remote controllers (control panel and separate remote controller), set one to Main and
the other to Sub.
The remote controllers are factory setting to Main, so you only have to change one remote
controller from Main to Sub. To change a remote controller from Main to Sub, proceed as follows:
3.1.1 Field Settings
The designation of the main and sub remote controllers can be swapped. Note that this change
requires turning the power OFF and then ON again.
Situation
Setting
Select
Switch Main Sub Controller
and press
Menu/OK
button.
Service
settings menu
is displayed.
Item 2 is
displayed.
Basic screen
is displayed.
Press and
hold the
Cancel
button for 4
seconds or
more.
Press the
Cancel
button.
Item 2 is
displayed.
Press the
Menu/OK
button.
Select
Main RC
or
Sub RC
using the
/
(Up/Down)
buttons, and then
press the
Menu/OK
button.
Press the
Cancel
button once.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...