SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
176
1.4.35 Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit,
this setting is unnecessary.
: Factory setting
1.4.36 Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote
controller/central unit when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
: Factory setting
1.4.37 Display of Error Codes on the Remote Controller
For BRC1E73 only
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
: Factory setting
1.4.38 Room Temperature Display
For BRC1E73 only
A "Detailed display screen" can be selected as the display screen. This setting is used if you do not
want "Room temperature display" to be shown on the "Detailed display screen".
: Factory setting
1.4.39 Thermistor Sensor for Auto Changeover and Setback Control by the
Remote Controller
For BRC1E73 only
Select a thermistor to utilize for the cool/heat mode automatic changeover and setback functions.
The sensed temperature will be displayed on the remote controller as the room temperature.
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
5
01
Normal
02
Individual
Mode
No.
First Code
No.
Second Code
No.
Contents
1b
4
01
—
02
Two-digit display
03
—
04
Four-digit display
Mode
No.
First Code
No.
Second Code
No.
Contents
1c
0
01
Not displayed.
02
Displayed.
Mode
No.
First Code
No.
Second Code
No.
Contents
1c
1
01
Utilize the return air thermistor
02
Utilize the remote controller thermistor
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...