SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
370
3.75 Climate Talk Communication System Combination Error
(After Initial Setting for Communication Completes)
Applicable
Models
CXTQ-TA
Error Code
UH-06
Method of Error
Detection
Detects the type of the devices constituted in Climate Talk Communication.
Error Decision
Conditions
The error decision is made when any of the following conditions is established once the initial
setting for communication with the gas furnace completes and after elapsing 4 minutes after the
power is turned ON.
Two or more gas furnaces are detected.
Any unit other than the gas furnace is detected.
Supposed
Causes
Connection of wrong devices
Two or more gas furnaces are connected to one CXTQ-TA.
Troubleshooting
YES
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
N
O
Replace the CXTQ-TA PCB
or the gas furnace PCB.
Connect the gas furnace of
proper combination. Do not
connect any other devices.
Any
device other
than the gas
furnace of proper
combination is connected
to 1 and 2
terminals of
X
8
A.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...