Troubleshooting by Error Code
SiUS342303E
271
Part 6 Service Diagnosis
3.19 Self-Cleaning Decoration Panel Abnormality
Applicable
Models
FXFQ-T (when self-cleaning decoration panel BYCQ125BGW1 is installed)
Error Code
AH
Method of Error
Detection
Error is detected by abnormal signal from the self-cleaning decoration panel.
Error Decision
Conditions
Any of the following conditions is met while the unit is in operation.
There is a transmission error between self-cleaning decoration panel and indoor unit.
Dust detection sensor (light receiving side) is short-circuited.
The total of fan operation time exceeds a specified value after dust collection sign display.
Limit switch does not detect when air filter rotates or air filter does not rotate.
Limit switch does not detect when damper opens (or closes) or damper does not work.
Filter auto clean operation does not complete even after a specified time has elapsed.
Filter auto clean operation does not start even after a specified time has elapsed.
Supposed
Causes
Transmission error (between self-cleaning decoration panel and indoor unit)
Dust detection sensor error
Dust collection sign
Air filter rotation error
Damper rotation error
Filter auto clean operation error
Filter auto clean operation start disabled error
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...