Field Setting from Outdoor Unit
SiUS342303E
209
Part 5 Field Settings and Test Operation
[2-65]: Heat pump lockout temperature
Heat pump would be locked out when the outdoor air temperature is smaller than the Heat Pump
Lockout Temperature below – this setting is only affective when heat pump lockout mode has
been set. Unit will switch to heat pump lockout.
Heat pump lockout
temperature
Fahrenheit (°F)
Celsius (°C)
0 (default)
–15
–26.1
1
–10
–23.3
2
–5
–20.5
3
0
–17.7
4
5
–15
5
10
–12.2
6
15
–9.4
7
20
–6.6
8
25
–3.8
9
30
–1.1
10
35
1.6
11
40
4.4
12
45
7.2
13
50
10
14
Forced heat pump lockout