SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
278
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Properly connect the
connector(s).
AH-07
Damper rotation error
Diagnosis Flowchart-5
YES
YES
Replace the harness.
Are the
connectors X6A and X10A
on the self-cleaning decoration
panel PCB properly
connected?
Is the harness broken?
NO
Properly attached the damper.
Is the damper
properly attached?
YES
YES
Remove the foreign matter.
Is there any
foreign matter in the damper
drive motor or drive
parts?
NO
YES
Replace the damper or
damper drive gear.
Is the damper or
damper drive gear
damaged?
NO
A
Go to the next page
NO
NO
Replace the limit switch.
Does limit switch have
continuity?
YES
YES
Replace the damper drive
motor.
Is the damper
drive motor damaged or
rotating poorly?
NO
YES
Remove the external factor.
Is there any
external factor other than the
error such as noise?
NO
Turn OFF the power supply and
then turn it ON again. (
1)
With the remote controller in stop
operation, perform filter auto clean
test operation. (
2)
NO
Properly connect the
connector.
Is the connector of
damper motor properly
connected?
YES
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...