Outline of Control (Indoor Unit)
Part 4 Functions and Control
144
Note(s)
9.13 Gas Furnace Control (CXTQ-TA Models)
Outline
When conditions for gas furnace operation are established, the system transits into gas furnace
operation, CXTQ-TA requires the gas furnace combustion heating.
Detail
The airflow rate during gas furnace operation depends on the intensity of combustion heating and
therefore may be different from the airflow setting displayed on the remote controller.
• Thermostat: ON
• Thermostat: OFF
Thermostat OFF
Thermostat ON
Heat p
u
mp operation
&
• Hot-water heater signal (from o
u
tdoor
u
nit): ON
• Compressor is s
u
spended
OR
• Hot-water heater signal (from o
u
tdoor
u
nit): OFF
• Compressor is operating
Gas f
u
rnace operation