SiUS342303E
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
198
[2-25]:
Night-time low noise operation level via the external control adaptor
If the system needs to run under night-time low noise operation conditions when an
external signal is sent to the unit, this setting defines the level of night-time low noise
that will be applied (3: Level 3 < 2: Level 2 < 1: Level 1).
This setting will only be effective when the optional external control adaptor
(DTA104A62) is installed and the setting [2-12] is activated.
Default value: 2
Change [2-25] to 1, 2 or 3 in function of required level.
[2-26]:
Night-time low noise operation start time
Change [2-26] to 1, 2 or 3 in function of required timing.
Default value: 2
Value
[2-26]
Start time automatic night-time low noise
operation (approximately)
1
About 8:00 PM
2 (default)
About 10:00 PM
3
About 12:00 AM
This setting is used in conjunction with setting [2-22].
[2-27]:
Night-time low noise operation stop time
Default value: 3
Value
[2-27]
Stop time automatic night-time low noise
operation (approximately)
1
About 6:00 AM
2
About 7:00 AM
3 (default)
About 8:00 AM
This setting is used in conjunction with setting [2-22].
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...