Troubleshooting by Error Code
SiUS342303E
331
Part 6 Service Diagnosis
3.53 Compressor Startup Abnormality
Applicable
Models
All outdoor unit models
Error Code
L9
Method of Error
Detection
Detect error according to the signal waveform of compressor.
Error Decision
Conditions
When compressor startup operation has not been completed.
Supposed
Causes
The stop valve is not opened
Defective compressor
Error in wire connections to compressor
Large differential pressure before compressor startup
Defective inverter PCB
Troubleshooting
YES
NO
NO
Apply power, and then restart
operation.
NO
Are the
leads of the
compressor
disconnected?
Connect the leads of the compressor.
YES
Is the
insulation
resistance of the relevant
compressor 100 k
Ω
or more?
Replace the compressor.
NO
YES
YES
YES
Refrigerant is
stagnated. (The unit is out
of power supply for more
than 6 hours.)
Solve the refrigerant stagnation.
(Power should be supplied for more
than 6 hours.)
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the stop valve
open?
Startup for
the first time after
installation?
Is a proper
amount of refrigerant
charged?
Open the stop valve.
NO
Charge a proper amount of
refrigerant.
NO
A
Go to the next page.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...