SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
366
3.72 System Not Set Yet
Applicable
Models
All indoor unit models
All outdoor unit models
Error Code
UF
Method of Error
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to that
of indoor units that have made changes in temperature.
Error Decision
Conditions
The error is determined as soon as the abnormality aforementioned is detected through checking
the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor
units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Troubleshooting
Is
indoor-outdoor
and outdoor-outdoor unit
transmission
w
iring
normal?
Is
indoor-outdoor
and outdoor-outdoor unit
transmission
w
iring
normal?
Replace the indoor unit
control PCB.
W
iring check operation may
not have been carried out
successfully.
After fixing incorrect
w
iring,
press and hold the
RETURN
(BS3)
button on the outdoor
unit main PCB for 5 seconds.
∗
The unit
w
ill not run for up to
12 minutes.
YES
N
O
YES
N
O
N
O
YES
Is the check
operation
carried out?
Open the stop valve.
YES
N
O
Are the stop
valves opened?
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...