4
|
Components
Service manual
56
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
a
b
a
c
a
4‑way valve pipe
b
4‑way valve
c
Putty
CAUTION
Overheating the valve will damage or destroy it.
6
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
7
Install the putty (if available) and the insulation (if available) in their original
location.
8
Install the 4‑way valve coil on the 4‑way valve body, see
53].
9
10
Add
refrigerant
to
the
refrigerant
circuit,
see
To install the 4-way valve coil
1
Install the 4‑way valve coil on the 4‑way valve body.
a
b
c
a
Screw
b
4‑way valve coil
c
4‑way valve body