4
|
Components
Service manual
102
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
232].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
97] of the indoor unit
main PCB and continue with the next
procedure.
To check the fuse of the indoor unit main PCB
INFORMATION
Fuse is ONLY available on the main PCB of the indoor units FTXTP-M and ATXTP-M.
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
97].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse
Blown fuse on the indoor unit main
PCB?
Action
Yes
Replace the blown fuse, see
No
97] of the indoor unit
main PCB and continue with the next
procedure.
Problem solved?
After all checking procedures listed above have been performed: