RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
a
a
b
a
a
Screw
b
Swing flap motor gearcase assembly
2
Connect the rocker arm to the swing raster.
c
a
b
a
Fan guard
b
Rocker arm
c
Swing raster
3
Tighten the 3 screws to fix the swing flap motor assembly.
4
Route the wiring harness through the harness retainers.
5
Install new tie straps to fix the wiring harness as needed.
6
Install the right side fan guard on the indoor unit (by clicking it on).
7
Install the secondary swing flap in the indoor unit (by clicking it on).
8
Install the main swing flap in the indoor unit (by clicking it on).
9
Install the main swing flap motor, see
174].
10
Install the switch box, see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.