4
|
Components
Service manual
165
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
a
b
c
a
Backside of the front panel
b
Fixing tab
c
Support
3
Close the front panel.
4
Gently press the front panel down until it clicks.
FTXTM-R, FTXTP-M and ATXTP-M units
1
Set the filters as they were.
2
Gently press the front panel at both sides and at the center until it clicks.
4.18 Reactor
4.18.1 Checking procedures
To perform an electrical check of the reactor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Visually check the reactor for any damage or burnt‑out components. If any
damage is found, replace the reactor, see
3
Check that the reactors are firmly installed on the main PCB.