4
|
Components
Service manual
88
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
2
Carefully click the complete humidity sensor PCB assembly out of the indoor
unit.
a
a
Humidity sensor PCB assembly
3
To install the humidity sensor PCB assembly, see
87].
To install the humidity sensor
1
Click the humidity sensor PCB assembly on the indoor unit.
a
a
Humidity sensor PCB assembly
2
Connect the harness to the humicity sensor PCB assembly.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove the humidity sensor wiring harness
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
144].
1
Disconnect the wiring harness from the humidity sensor (PCB).
2
Disconnect the wiring harness connector from the indoor unit main PCB.
3
Cut all tie straps (if any) that fix the wiring harness.
4
Route the wiring harness out of the harness retainers and remove the
humidity sensor wiring harness.