A
Indoor unit FTXTM-R
a
Connector S102
Is the measured voltage on the indoor
unit power PCB correct?
Action
Yes
Return to
109] of the indoor unit
power PCB and continue with the next
procedure.
No
Replace the indoor unit power PCB, see
113].
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
109].
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the indoor
unit power PCB installed?
Action
Yes
Return to
109] of the indoor unit
power PCB and continue with the next
procedure.
No
Replace the indoor unit power PCB, see
113].
To check the wiring of the indoor unit power PCB
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
109].
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.