4
|
Components
Service manual
68
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.3 Compressor thermal protector
4.3.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
144].
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
2
Remove the compressor thermal protection with bracket from the
compressor.