6
|
Maintenance
Service manual
222
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
6 Maintenance
NOTICE
General maintenance/inspection checklist.
Next to the maintenance instructions in
this chapter, a general maintenance/inspection checklist is also available on the
Daikin Business Portal (authentication required).
The general maintenance/inspection checklist is complementary to the instructions
in this chapter and can be used as a guideline and reporting template during
maintenance.
6.1 To clean the outdoor unit heat exchanger
1
Straighten the hair fins.
2
Clear the outdoor unit heat exchanger from dust, leaves,… using a fin-comb or
compressed air/N
2.
CAUTION
Avoid bending or damaging the hair fins of the outdoor unit heat exchanger during
the cleaning process.
Do NOT use a high‑pressure washer.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
6.2 To clean the indoor unit heat exchanger
1
Straighten the hair fins.
2
Clear the indoor unit heat exchanger from dust, … using a fin-comb or
compressed air/N
2.
CAUTION
Avoid bending or damaging the hair fins of the indoor unit heat exchanger during the
cleaning process.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.