4
|
Components
Service manual
206
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
4
Measure the output voltage between between the pins 4‑5 on the connector
S801 on the indoor unit main PCB.
Result:
The measured voltage MUST be 10~16 V DC.
Is the output voltage on the indoor unit
main PCB correct?
Action
Yes
Replace the wifi control PCB wiring
harness, see
No
Perform a check of the indoor unit main
PCB, see
97].
5
As there are no further check procedures for this component, perform a check
of the indoor unit main PCB to check if the wifi control PCB needs to be
replaced. See
97].
After complete check of the indoor unit
main PCB, is the problem solved?
Action
Yes
No further actions required.
No
Replace the wifi control PCB, see
4.23.2 Repair procedures
To remove the wifi control PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
144].
1
Disconnect the connector from the wifi control PCB.
2
Carefully click the complete wifi control PCB assembly out of the indoor unit.
a
A
A
Indoor unit FTXTA-B
a
Wifi control PCB assembly