4
|
Components
Service manual
185
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Pins
Measured resistance (Ω)
15-14
353.4~406.6
15-13
15-12
15-11
14-13
706.8~813.2
14-12
14-11
13-12
13-11
12-11
Swing raster motor resistance
measurements are correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Continue with the next step.
3
Remove the swing raster motor, see
186].
4
Measure the resistance between the following pins of the connector on the
swing raster motor.
Result:
The measurements MUST be as shown in the table below.
Pins
Measured resistance (Ω)
1-2
353.4~406.6
1-3
1-4
1-5
2-3
706.8~813.2
2-4
2-5
3-4
3-5
4-5
Swing raster motor resistance
measurements are correct?
Action
Yes
Replace the swing raster motor wiring
harness, see
186].
No
Replace the swing raster motor, see
186].