3
|
Troubleshooting
Service manual
49
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
3.6.10 Unit discharges white mist
Check
Detail
Check installation conditions.
▪
Humid site.
▪
Dirty site.
▪
Oil mist.
Check installation conditions.
Dirty heat exchanger.
Air filter.
Dirty air filter.
Fan motor.
Defective fan motor.
3.6.11 Humidifying problem
Check
Detail
Check the installation conditions.
▪
Insufficient heat insulation of duct.
▪
Ceiling too high for the floor size.
▪
Short circuit air flow caused by
insufficient installation space.
Check the installation.
▪
Is the proper humidification hose,
specified by Daikin, used?
▪
Breakage
or
blockage
of
the
humidification hose.
▪
Is the length of the humidification
hose correct (within specified length)?
▪
Is
setting
correct
for
the
humidification hose length?
Check the outdoor temperature and
humidity.
In case of extremely low outdoor
temperature or extremely low humidity,
the air outlet must be set at the height
of 1,8m.
Check the temperature setting.
Is the set temperature too high?
Check the ventilation timing.
Is the room ventilated too often?
Check the air filter.
Is the air filter clogged?
3.6.12 Swing flap does not operate
Symptom
Check
Detail
Swing flap does not
operate
Check swing flap motor
Some functions can force
the swing flap into a fixed
position, although swing
mode is selected on the
remote controller. This is
not a unit error, but a
control function to
prevent draft to the
customer.
Check indoor unit PCB
Connector connection