4.16.2 Repair procedures
To remove the outdoor unit heat exchanger
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
144].
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
216].
1
If needed, remove any parts to create more space for the removal of the heat
exchanger.
2
Remove the putty and insulation from the appropriate piping.
3
Remove the heat exchanger thermistor and air thermistor from their holder.
4
Remove the screws and remove the guard nets from the unit.
a
b
c
c
d
e
f g
a
Heat exchanger thermistor
b
Outdoor air thermistor
c
Guard net
d
Screw
e
Support plate
f
Heat exchanger pipe
g
Heat exchanger pipe
5
Remove the 2 screws and remove the support plate.
6
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
7
Wrap a wet rag around the components near the heat exchanger pipes. Heat
the brazing point of the heat exchanger pipes using an oxygen acetylene torch
and remove the heat exchanger pipes from the refrigerant pipes using pliers.