4
|
Components
Service manual
177
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
b
a
c
d
a
Main swing flap
b
Secondary swing flap
c
Screw (swing flap motor fixation)
d
Swing flap motor
3
Install and tighten the screw to fix the swing flap motor.
4
Install the secondary swing flap in the indoor unit (by clicking it on).
5
Install the main swing flap in the indoor unit (by clicking it on).
6
Install the switch box, see
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
FTXTP-M and ATXTP-M units
1
Install the swing flap motor in the correct location on the swing flap.
a
b
c
a
Cover
b
Screw
c
Swing flap motor
2
Install and tighten the screw to fix the swing flap motor.
3
Connect the connector to the swing flap motor.
4
Install the cover.