4
|
Components
Service manual
112
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
3
Check that the wiring corresponds with the wiring diagram, see
232].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
97] of the indoor unit
power PCB and continue with the next
procedure.
To check the fuse of the indoor unit main PCB
Prerequisite:
First perform all earlier checks of the indoor unit main PCB, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
A
A
Indoor unit FTXTA-B
a
Fuse F1U
a
A
A
Indoor unit FTXTM-R
a
Fuse F1U