![background image](http://html1.mh-extra.com/html/daikin/rxta30b2v1b/rxta30b2v1b_service-manual_4215663178.webp)
4
|
Components
Service manual
178
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To remove the swing flap motor wiring harness
FTXTM40R
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
144].
1
Remove the swing flap motor, see
INFORMATION
The swing flap motor wiring harness is also connected to the swing raster motor.
2
Put a small drain pan (or container) under the drain hose.
3
Remove the screw from the fixation bracket and pull the drain hose
downwards to remove it from the indoor unit.
a
b
c
a
Screw (drain hose)
b
Drain hose
c
Swing raster motor cover
4
Remove the swing raster motor cover.
5
Disconnect the wiring harness from the swing raster motor.
6
Remove the swing flap motor wiring harness.
7
To install the swing flap motor wiring harness, see
To install the swing flap motor wiring harness
FTXTM40R
1
Connect the wiring harness connector to the swing raster motor.
2
Install the swing raster motor cover.