4
|
Components
Service manual
171
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Pins
Measured resistance (Ω)
1-2
353.4~406.6
1-3
1-4
1-5
2-3
653.6~866.4
2-4
1-5
3-4
3-5
4-5
Swing flap motor resistance
measurements are correct?
Action
Yes
Replace the swing flap motor wiring
harness, see
174].
No
Replace the swing flap motor, see
FTXTM30R
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Disconnect the swing flap motor connector from the indoor unit main PCB.
2
Measure the resistance between the following pins of the motor connector.
Result:
The measurements MUST be as shown in the table below.
Pins
Measured resistance (Ω)
5-1
232.5~267.5
5-2
5-3
5-4
1-2
465~535
1-3
1-4
2-3
2-4
3-4