259
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
5
Press
.
6
Select 4.
7
Press
to confirm.
8
Press
.
9
Select 0 (0: fan ON, 1: fan OFF (factory setting)).
10
Press
to confirm.
To change auto restart ON to OFF
FTXTA-B and FTXTM-R units
INFORMATION
After power failure, the unit will automatically restart (default setting). It is possible
to switch OFF auto restart. For example: after a long power failure, generators have
to start‑up. As there is limited energy and the air conditioners do NOT have priority,
it is recommended to switch OFF auto restart.
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 10.
7
Press
to confirm.
8
Press
.
9
Select 0 (0: auto restart OFF, 1: auto restart ON (factory setting)).
10
Press
to confirm.
FTXTP-M and ATXTP-M units
INFORMATION
After power failure, the unit will automatically restart (default setting). It is possible
to switch OFF auto restart. For example: after a long power failure, generators have
to start‑up. As there is limited energy and the air conditioners do NOT have priority,
it is recommended to switch OFF auto restart.
1
Press
,
, and
simultaneously.
2
Press
.
3
Select SU.
4
Press
to confirm.
5
Press
.
6
Select 10.
7
Press
to confirm.
8
Press
.
9
Select 0 (0: auto restart OFF, 1: auto restart ON (factory setting)).
10
Press
to confirm.