Third party components
Service manual
221
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
To check the required space around the outdoor unit heat exchanger
1
Check if the space around the outdoor unit heat exchanger is sufficient. See
the installation manual for the required space specifications. Adjust as
needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.