4
|
Components
Service manual
167
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
c
b
c
a
c
c
a
L804
b
L803
c
Measuring point
Is the inductance measurement
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
167].
4.18.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See
4.19 Streamer unit
4.19.1 Checking procedures
1
As there is no specific check procedure for this component, first perform a
check of the indoor unit main PCB to check if the streamer unit needs to be
replaced. See
After complete check of the indoor unit
main PCB, is the problem solved?
Action
Yes
No further actions required.
No
Replace the streamer unit, see
167].
4.19.2 Repair procedures
To remove the streamer unit
Prerequisite:
Stop the unit operation via the user interface.