1.2 Document history
Rev.
Description of version / changes
Who
Date
1.0.0
First release
ABB
19.12.2012
1.0.1
Minor typos were corrected. TÜV certificate was added.
The text was changed in the document:
n
Safety I/O inputs and outputs are not electrically isolated from
the other electronic circuitry of the module.
n
The safety values for safety outputs of DX581-S (-XC) module
are only valid if the parameter “Detection” is set to "On".
n
DC (Diagnostic Coverage) for DX581-S (-XC) module shall be
≥ 94 %.
n
The clarification was added that the boot project update on
SM560-S is possible only if no boot project is loaded on SM560-
S.
n
Not more than one communication error (CE_CRC or
Host_CE_CRC output signals become equal to TRUE) per 100
hours is allowed to be acknowledged by the operator using
OA_C input signal without consulting the responsible safety per-
sonnel.
n
SM560-S cycle time shall be included three times instead of two
times in Safety Function Response Time calculation.
n
The values for input delay accuracy in Safety Function
Response Time calculation were updated.
n
Update of Appendix A with system data for AC500-S-XC.
ABB
08.03.2013
1.0.2
Words "Original Instructions" have been added to document title
ABB
17.04.2015
Introduction
Document history
30.03.2017
AC500-S
8