DiagCode
State Name
State Description and Output Setting
8005
ESPE Inter-
rupted
External Test
The automatic sensor test was faulty.
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has been acti-
vated at the FB (NoExternalTest = FALSE).
A TRUE signal at the sensor is required.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8006
End External
Test
The automatic sensor test was faulty.
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has been acti-
vated at the FB (NoExternalTest = FALSE).
The external manual test is complete.
The FB detected a complete sensor switching cycle (external controlled).
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8010
ESPE Free No
Test
The FB has not detected a safety demand.
The sensor has not been tested automatically.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = TRUE
TestExecuted = FALSE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib