7.4.4 Program example
Activate
S _EStopIn
Ready
S _ES topOut
SF_Emergen cyStop
EStop_ S1
S _StartReset
S _AutoReset
Error
DiagCode
Reset
S0_ Reset
FALS E
FALS E
TRUE
S1_S _ES topIn
Activate
S_ OutControl
Ready
S_EDM _Out
SF_EDM
EDM_K1_K2
S_ EDM1
S_ EDM2
DiagCode
MonitoringTim e
S_ StartReset
Reset
Error
Activate
S_S afeControl
Ready
S _OutControl
SF_OutCon trol
OC_K1_K2
ProcessControl
StaticControl
DiagCode
S_S tartReset
S_A utoReset
Reset
Error
T#200 m s
S0_ Reset
FALSE
K1 _S_E DM 1
K2 _S_E DM 2
S_EDM _Out_EDM _K1 _K2
S0_Reset
TRUE
TRUE
FALS E
Activate
S _Butt on1
Ready
S_TwoHandOut
SF_TwoHand Con trolType II
THC_S2_S3
S _Butt on2
Error
DiagCode
Process
S 2_S_S witch1
S 3_S_S witch2
TRUE
TRU E
SAFEBOOL _TO_BOOL
Fig. 140: Application Program TwoHand Control with EDM
7.4.5 Additional notes
This example can also be used with the SF_TwoHandControlTypeIII.
The diagnostic information retrieval has not been covered in this example. For this, refer to
“Additional notes” on page 428
. The input Activate has been set to TRUE via its input for clarity sake. How-
ever, in an application this can be replaced by a variable.
Safety application examples
Example 3: Two-hand control > Additional notes
30.03.2017
AC500-S
440