6.5.2.2
DI581-S Safety I/O tables
Fig. 129: The “DI581-S Configuration” Tab is a readback view for iParameters set in “DI581-S” Tab.
1
“DI581-S” Tab
2
“DI581-S Configuration” Tab
1.
Compare that “Check supply” parameters have the same values “On” or “Off” (English settings) in both
“DI581-S” and “DI581-S Configuration” tabs.
2.
Refer to “DI581-S” tab and calculate “Input channel 0” decimal equivalent
(Dec_InputChannel0)
as:
Dec_InputChannel0 = Configuration Test_Pulse Input_Delay_Value
where
Configuration_Value:
0
➔
Not used
1
➔
1 channel
2
➔
2 channel equivalent
3
➔
2 channel antivalent
Test_Pulse_Value:
0
➔
Disabled
8
➔
Enabled
Input_Delay_Value:
16
➔
1 ms
32
➔
2 ms
48
➔
5 ms
64
➔
10 ms
80
➔
15 ms
96
➔
30 ms
112
➔
50 ms
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017