DiagCode
State Name
State Description and Output Setting
8020
Test Request
The automatic sensor test is active. Test Timer is started first time.
The transmitter signal of the sensor is switched off by the FB.
The signal of the receiver must follow the signal of the transmitter.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = FALSE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8030
Test Active
The automatic sensor test is active. Test Timer is started second time.
The transmitter signal of the sensor is switched on by the FB.
The signal of the receiver must follow the signal of the transmitter.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
8000
ESPE Free
Test ok
The FB has not detected a safety demand.
The sensor was automatically tested.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = TRUE
TestExecuted = TRUE
Error = FALSE