![ABB AC500-S Safety User Manual Download Page 49](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916049.webp)
DEBUG STOP
SM560-S
DIAG
PWR
RUN
I-ERR
E-ERR
Without light error E3 or warning E4
SM560-S
DIAG
PWR
RUN
I-ERR
E-ERR
With light error E3 or warning E4
In this state, a user is able to intervene in safety program execution by setting breakpoints, etc., similar to
DEBUG RUN state. The safety application program is not executed in DEBUG STOP state. The PROFIsafe
F-Host of SM560-S sends PROFIsafe telegrams with fail-safe “0” values and sets FV_activated for all Safety
I/O modules.
If CoDeSys online service
“RUN”
is called in the safety application program, SM560-S switches to DEBUG
RUN state.
All CoDeSys online services are available in this state.
In case of CoDeSys online commands
“Step in”
,
“Step over”
,
“Single cycle”
and when the breakpoint is
reached, there is a switch between DEBUG RUN and DEBUG STOP states (
Ä
14).
One can go back to a safe RUN state only using powering off/on or
“reboot”
PLC Browser command on
PM5xx Non-safety CPU.
AC500-S Safety Modules
SM560-S Safety CPU > SM560-S module states
30.03.2017
AC500-S