![ABB AC500-S Safety User Manual Download Page 321](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916321.webp)
Function Block-Specific Error and Status Codes
Table 61: FB-specific error codes
DiagCode
State Name
State Description and Output Setting
C001
Reset Error1
Static Reset detected in state 8001.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = TRUE
C002
Reset Error 2
Static Reset detected in state C004.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = TRUE
C003
Reset Error 3
Static Reset detected in state 8011.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = TRUE
C004
Safety Lost
Safety lost, guard opened or guard unlocked.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = TRUE
Table 62: FB-specific status codes (no error):
DiagCode
State Name
State Description and Output Setting
0000
Idle
The function block is not active (initial state).
Ready = FALSE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = FALSE
8000
Guard Closed
and Locked
Guard is locked.
Ready = TRUE
S_GuardLocked = TRUE
S_UnlockGuard = FALSE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S