DiagCode
State Name
State Description and Output Setting
C071
Reset Error 41 Static Reset signal in state C070.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C081
Reset Error 42 Static Reset signal in state C080.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C091
Reset Error 43 Static Reset signal in state C090.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C010
EDM Error 11
The signal at EDM1 is not valid in the initial actuator state. In state 8010
the EDM1 signal is FALSE when enabling S_OutControl.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C020
EDM Error 12
The signal at EDM2 is not valid in the initial actuator state. In state 8010
the EDM2 signal is FALSE when enabling S_OutControl.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C030
EDM Error 13
The signals at EDM1 and EDM2 are not valid in the initial actuator states.
In state 8010 the EDM1 and EDM2 signals are FALSE when enabling
S_OutControl.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C040
EDM Error 21
The signal at EDM1 is not valid in the initial actuator state. In state 8010
the EDM1 signal is FALSE and the monitoring time has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE