Name
Data Type
Initial Value
Description, Parameter Values
Reset
BOOL
FALSE
Table 31 “General Input Parameters”
MaxMutingTime
TIME
T#0s
Constant 0 .. 10 min;
Maximum time for complete muting sequence,
timer started when first muting sensor is actuated.
VAR_OUTPUT
Ready
BOOL
FALSE
Table 32 “General Output Parameters”
S_AOPD_Out
BOOL
FALSE
Safety related output, indicates status of the
muted guard.
FALSE: AOPD protection field interrupted and
muting not active.
TRUE: AOPD protection field not interrupted or
muting active.
S_MutingActive
BOOL
FALSE
Indicates status of Muting process.
FALSE: Muting not active.
TRUE: Muting active.
Error
BOOL
FALSE
Table 32 “General Output Parameters”
DiagCode
WORD
16#0000
Table 32 “General Output Parameters”
Notes: A short circuit in the muting sensor signals, or a functional application error to supply these signals,
are not detected by this FB but interpreted as incorrect muting sequence. However, this condition should not
lead to unwanted muting. The user should take care to include this in his risk analysis.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
337