DiagCode
State Name
State Description and Output Setting
8003
Wait for Reset Waiting for rising trigger at Reset.
Ready = TRUE
S_GuardMonitoring = FALSE
Error = FALSE
8012
Guard
Opened
Guard completely opened.
Ready = TRUE
S_GuardMonitoring = FALSE
Error = FALSE
8004
Wait for
GuardSwitch2
S_GuardSwitch1 has been switched to TRUE - waiting for S_Guard-
Switch2; discrepancy timer started.
Ready = TRUE
S_GuardMonitoring = FALSE
Error = FALSE
8014
Wait for
GuardSwitch1
S_GuardSwitch2 has been switched to TRUE - waiting for S_Guard-
Switch1; discrepancy timer started.
Ready = TRUE
S_GuardMonitoring = FALSE
Error = FALSE
8005
Guard Closed
Guard closed. Waiting for Reset, if S_AutoReset = FALSE.
Ready = TRUE
S_GuardMonitoring = FALSE
Error = FALSE
4.6.6.8
SF_TwoHandControlTypeII
Standards
Requirements
EN 574: 1996
Clause 4, Table 1, Type II.
5.1 Use of both hands / simultaneous actuation.
5.2 Relationship between output signal and input signals.
5.3 Completion of the output signal.
5.6 Reinitiation of the output signal.
6.3 Use of DIN EN 954-1 category 3 (Can only be realized by NO and NC switches
together with antivalent processing)
ISO 12100-2:
2003
4.11.4: Restart following power failure/spontaneous restart
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017