![ABB AC500-S Safety User Manual Download Page 286](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916286.webp)
Function Block-Specific Error and Status Codes
Table 43: FB-specific error codes
DiagCode
State Name
State Description and Output Setting
C001
Error
Short-circuit
The FB detected that two or more S_ModeX are TRUE, e.g., short-circuit
of cables.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
C002
Error
Open-circuit
The FB detected that all S_ModeX are FALSE: The period following a
falling S_ModeX trigger exceeds ModeMonitorTime, e.g., open-circuit of
cables.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
C003
Reset Error 1
Static Reset signal detected in state C001.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
C004
Reset Error 2
Static Reset signal detected in state C002.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
286