Table 36: FB Name: SF_Equivalent
Name
Data Type
Initial Value
Description, Parameter Values
VAR_INPUT
Activate
BOOL
FALSE
Table 31 “General Input Parameters”
S_ChannelA
BOOL
FALSE
Variable.
Input A for logical connection.
FALSE: Contact A open
TRUE: Contact A closed.
S_ChannelB
BOOL
FALSE
Variable.
Input B for logical connection.
FALSE: Contact B open
TRUE: Contact B closed.
DiscrepancyTime
TIME
T#0ms
Constant.
Maximum monitoring time for discrepancy status
of both inputs.
VAR_OUTPUT
Ready
BOOL
FALSE
Table 32 “General Output Parameters”
S_EquivalentOut
BOOL
FALSE
Safety related output
FALSE: Minimum of one input signal = "FALSE"
or status change outside of monitoring time.
TRUE: Both input signals "active" and status
change within monitoring time.
Error
BOOL
FALSE
Table 32 “General Output Parameters”
DiagCode
WORD
16#0000
Table 32 “General Output Parameters”
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S