Function Block-Specific Error and Status Codes
Table 73: FB-specific error codes
DiagCode
State Name
State Description and Output Setting
C001
Reset Error 1
Static Reset condition detected after FB activation in state 8001.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
C002
Reset Error 2
Static Reset condition detected in state 8003.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
C003
Error Muting
Lamp
Error detected in muting lamp.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
CYx4
Error Muting
sequence
Error detected in muting sequence state 8000, 8011, 8311.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Y = Status in the sequence
C0x4 = Error occurred in state 8000
C1x4 = Error occurred in state 8011
C2x4 = Error occurred in state 8311
CFx4 = Muting Enable missing
x = Status of the sensors when error occurred (4 bits: LSB = MS_11; next
to LSB = MS_12).
C005
Parameter
Error
DiscTimeEntry or MaxMutingTime value out of range.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
364